帮助 关于我们

返回检索结果

电化学腐蚀对翅片管换热器性能的影响
Effect of electrochemical corrosion on performance of tube-fin heat exchanger

查看参考文献15篇

赵宇 1   王勤韧 1   陈江平 1 *   申隽 2  
文摘 翅片管换热器的铜管与铝翅片之间容易发生电化学反应,在铝翅片表面形成一层三氧化二铝,增大换热器传热热阻,影响换热器乃至整个空调系统的性能.对翅片管换热器分别进行48 h和96 h的盐雾腐蚀实验,然后对腐蚀前后的实验样件测试其传热及压降特性,结果表明,翅片管蒸发器经盐雾腐蚀以后,其风阻变化在5 Pa以内,而换热量最多会降低12.5%,总的传热系数最多会减少16.6%,传热热阻最多会增加20%.
其他语种文摘 Electrochemical corrosion takes place between the copper tube and aluminum fin of tube-fin heat exchanger easily,forming a high thermal resistance layer of Al_2O_3.Therefore,the performance of the heat exchanger and the entire air conditioning system will be affected.In this paper,48 h and 96 h salt spray corrosion tests were made on the tube-fin heat exchanger respectively.And the performance of the heat exchanger before and after salt spray corrosion was tested.It was found that the change of air pressure drop was less than 5 Pa.The capacity and overall heat transfer coefficient of the heat exchanger decreased by 12.5% and 16.6% after corrosion respectively.The thermal resistance of the heat exchanger increased by 20% at most.
来源 化工学报 ,2010,61(1):22-26 【核心库】
关键词 翅片管换热器 ; 电化学腐蚀 ; 传热系数 ; 热阻
地址

1. 上海交通大学制冷与低温工程研究所, 上海, 200240  

2. 国际铜业协会广州代表处, 广东, 广州, 510620

语种 中文
文献类型 研究性论文
ISSN 0438-1157
学科 一般工业技术
文献收藏号 CSCD:3804432

参考文献 共 15 共1页

1.  徐志明. 管式换热器积灰特性的实验研究. 工程热物理学报,2002,23(2):203-205 被引 7    
2.  Li Y. Impact of fouling on the performance of filter-evaporator combinations. International Journal of Refrigeration,2007,30(3):489-498 被引 4    
3.  Siegel J A. Predicting particle deposition on HVAC heat exchangers. Atmospheric Environment,2003,37(39):5587-5596 被引 6    
4.  浦晖. 微生物污垢对翅片管换热器空气侧换热和压降特性的影响. 上海交通大学学报,2008,42(3):404-408 被引 5    
5.  Abd-Elhady M S. Optimization of flow direction to minimize particulate fouling of heat exchangers. Heat Transfer Engineering,2009,30(10/11):895-902 被引 5    
6.  Casanueva J F. Portable pilot plant for evaluating marine biofouling growth and control in heat exchangers-condensers. Water Science and Technology,2003,47(5):99-104 被引 2    
7.  Nebot E. In situ experimental study for the optimization of chlorine dosage in seawater cooling systems. Applied Tnermal Engineering,2006,26(16):1893-1900 被引 11    
8.  Kuznicka B. Erosion-corrosion of heat exchanger tubes. ENGINEERING FAILURE ANALYSIS,2009,16:2382-2387 被引 6    
9.  衡世权. The formation mechanism and preventive measure of heat exchanger corrosion fouling. 节能,2004(4):28-30 被引 1    
10.  何源. Refrigeration unit heat interchanger corrosion and prevention. 洁净与空调技术,2008(4):36-39 被引 1    
11.  王育忠. Reasons and countermeasures of corrosion for aluminum tube heat-exchanger. 石化技术,2005,12(3):53-54 被引 2    
12.  . GB/T 10125-1997 被引 1    
13.  Moffat R J. Describing the uncertainties in experimental results. Experimental Thermal and Fluid Science,1998,1(1):3-17 被引 378    
14.  . JB/T 6914-93 被引 1    
15.  Wang C C. Data reduction for air-side performance of fin-and-tube heat exchangers. Experimental Thermal and Fluid Science,2000,21(4):218-226 被引 12    
引证文献 4

1 胡兵 温度交变对翅片管换热器性能影响的实验研究 制冷学报,2011,32(2):19-22
被引 1

2 詹飞龙 空调换热器长效性能衰减的研究进展 制冷学报,2015,36(3):17-23,40
被引 10

显示所有4篇文献

论文科学数据集