地下建筑通风降氡效率研究
A study of reducing radon level by ventilation in underground space

查看参考文献5篇

文摘 用Model 1027型连续测氡仪对中国呼和浩特市某地下建筑作通风降氡效率研究.该地下室有4种通风方式:进风(只开进风机,简称B)、排风(只开排风机,简称P)、进排同时(同时开启进风机和排风机,简称BSP)、进排轮流(轮流开启进风机和排风机,简称BRP).比较4种通风方式的降氡效率,得出进排同时降氡效果最好.用此方式分别每天通风1、2、3 h,观察24 h氡浓度变化,得出每天早晨通风2 h,足以满足氡浓度8 h维持在国家限定标准以下.
其他语种文摘 Using Model 1027 continuous radon monitor, a test of reducing radon level by ventilation in underground space was done. Four different types of ventilation, i.e. by air pump (P), by air intake blower (B), by air pump and air intake blower simultaneously (PBS), and by air pump and air intake blower in turn (PBT), were examined. We found that efficiency of PBS is the highest among these ventilation types. Having ventilated the underground space with PBS for 1, 2 or 3 hours in three different days, and having observed the radon concentration change in the following 24 hours, we can conclude that it is safe for people to stay there during the eight working hours if the underground space is ventilated for 2 hours everyday in the morning.
来源 核技术 ,2005,28(12):954-956 【核心库】
关键词 ; 地下建筑 ; 通风
地址

中国科学院地球化学研究所, 环境地球化学国家重点实验室, 贵州, 贵阳, 550002

语种 中文
文献类型 研究性论文
ISSN 0253-3219
学科 环境科学基础理论
文献收藏号 CSCD:2045356

参考文献 共 5 共1页

1.  Miles J. Journal of Hazardous Materials,1988,61:53-58 CSCD被引 3    
2.  杨文堦. 中国辐射卫生,1999,3(2):93 CSCD被引 2    
3.  Anastasiou T H. Journal of Environmental Radioactivity,2003,68:159-169 CSCD被引 1    
4.  赵中振. 中华放射医学与防护杂志,1988,8(增刊2):31-35 CSCD被引 1    
5.  张洪杰. 内蒙古环境保护,1996,8(1):29-31 CSCD被引 1    
引证文献 1

1 李晓燕 我国部分城市地下工程空气中的氡水平 辐射防护,2007,27(6):368-374
CSCD被引 3

显示所有1篇文献